The TSi Power Corporation Home Page White Papers On Power Protection Strategies and Technologies Press Releases and News on TSi Power Corporation TSi Power & Surge Protection Products Overview Line Conditioners, Automatic Voltage Regulators, Low-Impedance and Ferroresonant Isolation Transformers Ac Automatic Voltage Regulators, Precision PWM, Tap-Switching and Ferroresonant Topologies Unipolar PWM Sine Wave Output Dc to Ac Inverters Automatic Transfer Switches For Enabling Redundant Power Sources e.g. 2 UPS Indoor Uninterruptible Power Systems Outdoor UPS With Extreme Wide Temperature Batteries for Harsh Environments Accessories for TSi Products, such as Rack-mounting Kits, Extra Battery Cabinets, etc. Pricing, RFQ's, RFP's and Getting Formal Quotations Frequently Asked Questions URL Links to some of TSi Power's Favorite Websites URL Link to the Free Adobe Acrobat PDF Reader Download Page

 * Best Viewed In Internet Explorer

 

The Merits of a
Standby UPS with a
Modified Sinewave Output



By Nam Paik, TSi Power
 

White Paper On The Merits Of A Standby UPS With A Modified Sinewave Output. Features and Benefits, advantages, and why standby is popular.

Click here for the White Paper in
printer friendly Adobe Acrobat PDF Format


O
f the 3 major UPS architectures (e.g. Standby, Ferroresonant On-Line, and Double-Conversion
On-Line)
, the Standby UPS features the following advantages:

Features Benefits

1.

Extremely high power efficiency, Typically above 97%. Lowest operating cost in terms of electric use – only 1/10 of double-conversion on-line UPS.

2.

Air exhaust fan is normally off since very little heat is generated. Quiet operation. Does not add to air conditioning loads.

3.

The inverter circuit is normally off. Very quiet operation and the highest MTBF (mean-time-between failure) due to the lowest voltage, current and temperature of its internal parts.

4.

Cooler internal operating temperature. Battery lifetime is approximately twice that of an on-line type UPS.

5.

Output waveform is normally a sinewave. The inverter waveform is a modified square-wave, generated only during power outages. The pulse-width-modified and optimized peak-voltage modified square waveform is actually more beneficial for switchmode power supplies.

6.

Simplest and most economical UPS design. Simple design with the lowest parts count. Means lowest purchase price and maintenance costs. Repair procedures are quick and easy.

7.

The switchover time of some high-quality Standby UPS is less than 1ms. The ride-through of typical switchmode power supplies is 10 to 20 ms. A fast 1ms switchover time guarantees glitch-free transfers.

The above mentioned merits of a Standby UPS with modified square-wave inverter output are the reasons for the popularity of the standby architecture in UPS sized under 1KVA. In fact, the vast majority (over 80%) of UPS under 1KVA being used today are of the Standby type with millions installed in the USA alone. 

Back to Top 

             

TSi Power Corporation ~ 1103 West Pierce Ave ~ Antigo, Wisconsin 54409 ~ Direct 715.623.0636 ~ 800.874.3160 (USA)
Fax 715.623.2426 ~ e-mail ~ sales@tsipower.com  ~  michaelg@carebase.com for comments/feedback on web site.
Privacy Statement    Copyright © 2001-2006 TSi Power Corporation

                                                        Hit Counter