* Best Viewed In Internet Explorer
| |
VRp
Series
9kVA and
15kVA
220/380V and 230/400V
Three Phase Wye
Precision,
no-break, PWM
automatic voltage regulator
ac line conditioner
with
automatic bypass
|
 |
Precision
Fast-PWM Mains Voltage Correction
TSi Power’s VRp automatic precision regulator
line conditioner provides output voltage within plus/minus 3% of
nominal, for input voltage that varies between 185 to 265VAC, per phase.
There
is no switching of taps or otherwise a break in the power path thanks to
continuous PWM (Pulse-Width-Modulation) switching of a buck-boost transformer.
Typical VRp
Applications
Designed for applications that require absolutely stable,
high-reliability power, without switching components in the power path.
Applications include, but are not limited to: analytical
equipment, radio and TV broadcast equipment, mobile broadcast vans,
industrial controllers (PLC), milking machines, lithographic equipment,
recording studio equipment and electrolysis equipment.
Key Benefits of
the VRp Series
The low-weight, high efficiency VRp is easy to install in any
environment. The automatic bypass assures that connected equipment will
not shut down, even if VRp fails. VRp is compatible with all loads as it
does not switch any components in the power path. VRp’s ultra-low
impedance assures stability even with the most demanding loads.
How the VRp
Series Precision Electronic AVR Works
The high frequency IGBT driven converter takes the
incoming AC power, measures against the nominal voltage and adds or
subtracts voltage, 10,000 times per cycle, to achieve the nominal output
voltage +/-3%.
The Automatic Bypass will be activated when there is a fault
condition. Green LED indicates Normal (regulating mode operation),
Yellow LED indicates Bypass (non-regulated output), and the Red LED indicates a Fault condition. |
| |
SPECIFICATIONS |
VRp-9000 |
VRp-15000 |
| |
Electrical |
|
Capacity in VA (Watts) |
9 kVA (9000 watts) |
15 kVA (15000 watts) |
| |
Regulator engine |
High
Frequency 10kHz IGBT Driven Voltage Regulation Converter |
| |
Input |
| |
Nominal voltage |
Three phase wye: 220/380V or 230/400 volts ac |
| |
Normal operating voltage |
Range: 185
~ 265 volts ac |
| |
Maximum operating range |
160
~ 300 vac (with reduced output capacity & wider regulation) |
| |
Nominal frequency |
47
~ 63
Hz |
| |
Overcurrent protection |
Input circuit
breaker |
| |
Circuit breaker rating |
3 x 20 amps (ganged) |
3 x 30 amps (ganged) |
| |
Input wire size |
AWG 12 (3.3 square mm) |
AWG 10 (5.3 square mm) |
| |
Ac input connection |
Input wire terminal block (L1, L2, L3,
neutral and ground wires) provided. |
| |
Output |
| |
Nominal voltage |
Three phase wye: 220/380V or 230/400 volts ac (factory set) |
| |
Power efficiency |
Better than 96%
(under all load conditions) |
| |
Voltage regulation |
Nominal +/-3% maximum under 0 to 100% load
and input of 185~265V |
| |
Relaxed voltage regulation |
192 ~ 240 volts ac over wider input range of
160 ~ 300vac |
| |
Automatic bypass |
Automatic
bypass will be activated when there is a fault condition. |
| |
System status indicators |
System status LED’s provided as follows:
Green LED (blinking)indicates Normal (regulating mode operation);
Yellow LED (blinking) indicates Bypass (non-regulated output);
Red LED indicates Overload (system may shut down).
|
| |
Surge test conditions |
Per ANSI/IEEE C62.41-1991 6kV normal-mode injection |
| |
Surge let-through voltages |
Category A3, Ring wave, 200A: L-N: 30V
Cat. B3, Combination wave, 3000A: L-N: 200V
Note: Unit
should be installed as close as possible (within 30’) of
the neutral-to-ground bond at the service entrance, in order
to minimize potential difference between neutral and ground.
A separate isolation transformer is recommended for
installations where distance exceeds above, or for
grounding systems without a neutral-to-ground bond.
|
| |
Ac output connection |
Output wire terminal block (L1, L2,
L3, neutral and ground) |
| |
Physical |
| |
Dimensions |
610mm(24")wide x 710mm(28")high x 560mm(22")deep |
| |
Weight |
73 kg (160 lbs) |
86 kg (190 lbs) |
| |
Safety |
| |
Agency approvals |
Designed
to meet UL/cUL1950 and IEC 60950 standards. |
| |
Environmental |
| |
Ambient temperature |
0
to +40°C, 90%
Relative Humidity (non-condensing), to 10,000ft. (3km) |
| |
Warranty |
| |
Warranty |
Two year limited warranty, parts and labor |
|
TSi's ongoing product
improvement process makes specifications subject
to change. Other
companies product names herein are for identification purposes only, and
may be trademarks of their respective companies. |
VRp Series
Precision AVR System
Architecture

TSi Power also manufactures
custom automatic voltage regulators.
For special applications, please call.
Back to Top
|