* Best Viewed In Internet Explorer
| |
| This
automatic voltage regulator provides stable power even when the AC mains
or back-up generator voltage is extremely low or high.
Typical
Applications For The SLc Series
SLc Series conditioners provide
low-cost AC line protection for computers, point-of-sale terminals,
copiers, data acquisition and control systems, as well as other data
processing equipment. SLc’s can also be used to protect low-cost stand-by UPS to prevent
discharge of UPS batteries due to low- or high-voltage transfer to inverter.
Key SLc Series
Benefits
TSi Power’s SLc Series regulated
output protects switch-mode power supplies from failure caused by
unstable AC mains. SLc provides three-way surge protection and reduction
of surge voltage. The SLc line conditioner can be used
between a UPS and the AC mains to provide even greater protection for
the connected equipment, while saving the UPS's internal batteries for
true black-outs.
How The SLc Series 4 Stage Automatic Voltage Regulator Works
The
SLc Series incorporates a four-winding auto-transformer, which
provides four levels of line regulation: two boost-stage and one
buck-stage. Even when the input voltage varies between 150 to 280V, the
output is regulated to within 200 and 250V, well within the range of
most equipment.
SLc operation is monitored by 4 status LED’s,
indicating normal, boost 1, boost 2 and buck stages of voltage
regulation. The front panel power switch turns the SLc on and supplies
power to the equipment. |
| |
SPECIFICATIONS |
SLc-600 |
SLc-1200 |
SLc-1800 |
| |
Electrical |
|
Capacity in VA (Watts) |
600VA
(600W) |
1200
VA (1200W) |
1800
VA (1800W) |
| |
Transformer Type |
Four
Winding Auto-Transformer |
| |
Input |
| |
Nominal Voltage |
230
Volts AC |
| |
Operating Voltage |
150-280 Volts AC |
| |
Nominal Frequency |
50/60
Hz |
| |
AC Input Cord |
6
Foot long AC power cord with IEC-320 plug |
| |
Output |
| |
AC Output Voltage |
200
~ 250
Volts AC |
| |
Surge Protection |
Three-way stage surge protection system. |
| |
Surge Test Conditions |
Per
ANSI/IEEE C62.41-1991 test pulse,
Category A3, Ring Wave, 6000V, 200A
Test pulse injection: Line-neutral, line-ground, and neutral-ground. |
| |
Surge Let-Through Voltages |
Remnant Voltage: L-N: 15V, L-G: 15V, N-G: 400V |
| |
Power Efficiency |
>
97% at full load |
| |
Power On/Off Switch |
On/Off
Rocker Power Switch |
| |
Response Time |
Transfers
to new stage within 20 cycles of new AC input voltage. |
| |
Transfer Time |
Less
than 4 mS between stages. |
| |
Hysteresis |
6V
minimum. Prevents unnecessary switch-overs
due to momentary AC sags and brownouts. |
| |
Indicators |
4
status LED's indicating Normal, Boost 1,
Boost 2, and Buck stages of voltage regulation. |
| |
AC Receptacles |
4
IEC-320, E Option) or 2 Schuko (EC Option) |
| |
Audible Noise |
Minimal |
| |
Physical |
| |
Dimensions |
6"(152mm)Wide x
4"(102mm)High x 8"(203mm)Deep |
| |
Weight |
8
lbs. (3.6 kgs.) |
11
lbs. (5 kgs.) |
15
lbs. (6.8 kgs.) |
| |
Safety |
| |
Safety Standards |
Designed
to meet UL
& IEC standards. |
| |
Environmental |
| |
Ambient Temperature |
0
to +40°C,
90% Relative Humidity (non-condensing @ 25.5°C) |
| |
Warranty |
| |
Warranty |
2
Year Limited Warranty, Parts & Labor |
|
TSi's ongoing product
improvement process makes specifications subject to change. Other
companies product names herein are for identification purposes only, and
may be trademarks of their respective companies. |
SLc Series
230V 4
Tap AVR System
Architecture

TSi Power also manufactures
custom voltage regulators.
For special applications, please call.
Back To Top
|